2202
FlexTop 2202 Temperatuur Omvormer (Exi)
Specifications
Input | Pt100 to IEC/DIN/EN 60 751-2 |
Sensor type | 2-, 3- or 4-wires |
Accuracy | ±0.25°C t< 100°C /< 0.1% of signal span |
RTD measuring current | 0.3 mA, continuously |
Measuring range | -200...850°C |
Measuring unit | °C or °F |
Minimum span | 25°C |
Sensor break detection | > 875°C |
Short close detection | < -225°C |
Error detection delay | < 10 sec. |
Resolution | 14 bit |
Output signal: | 4...20 mA, 2-wire |
Up/Down scaling limits | 23 mA/3.5 mA |
Protection | +/- 35 Vdc |
Load equation | RL < (Vcc - 8)/23 [kOhm] |
Generic standards | EN 61000-6-3, EN 61000-6-2 |
Product standards | EN 61326 |
NAMUR | NAMUR NE21 |
Approval | Ex ia IIC T5/T6, ATEX II 1G |
Temperature class | T1...T5: -40 < Tamb < 85°CT6: -40 < Tamb < 50°C |
Operating temperature | -40...85°C |
Humidity | < 98% RH, cond. (IEC 68-2-38) |
Long-term test | IEC 770 6.3.2 |
Vibrations | GL, test 2 (IEC 68-2-6) |
Dimensions | ø44 x 19 mm |
Protection class | Housing: IP 40 |
Flextop 2201 | FlexTop 2201 is discontinued and replaced with the FlexTop 2202 |